100TR-Condensing Unit With AHU-27000cfm
Brand :
TAHVIEH-AZARBAD
Model :
TA-IND-CU-100-2D
Main Features
Designing the units based on project needs and cooling load, relative humidity, etc.
Availability of all parts during the warranty and after-sales service period and quick and easy access to the company or after-sales service experts
Installing a AHU fan with static and dynamic balance
Using the best brand of compressors and raw materials in the manufacture of units
Description
Data Sheet
Data
Unit
Characteristic
TA-IND-CU-100-2D
-
Condensing Unit Model
243.6
Kw
Actual Cooling Load
69.2
Ton
Actual Cooling Load
R134a
-
Refrigerant
Screw
-
Type Of Compressors
2
Pcs
Number Of Compressor
BITZER
-
Compressor Brand
CSH6583-50Y-40P
-
Compressor Model
6
Set
Condenser Fan Quantity
80
Cm
Condenser Fan Diameter
3Row/10Fpi
Row/Fpi
Condenser Coil Row/Fpi
3/8
Inch
Condenser Coil Tube Size
115
Kw
Condensing Unit Power Consumption
450x250x220
Cm
Condensing Unit Dimension (LxWxH)
TA-IND-AHU-27000
-
Air Handling Unit Model
27000
CFM
AHU Supply Air Flow Rate
DX
-
Type Of Evaporator
6Row/10Fpi
Row/Fpi
Evaporator Coil Row/Fpi
5/8
Inch
Evaporator Coil Tube Size
2
No.
Number Of Circuit at Evaporator
Electrical or Hot Water
-
Heating Coil Type
Based on customer request
BTU/H
Heating Load
550~450
FPM
Air Velocity On Coils
Aluminum Washable
-
AHU-First Bed Filter
Pleated (optional)
-
AHU-Second Bed Filter
Bag Filter (Optional)
-
AHU-Third Bed Filter
1450
RPM
Motor Speed
22
Kw
AHU Motor Power
80
Cm
AHU Fan Diameter
1
Set
Number Of AHU Electro fan
1
In-Wg
External Pressure Drop
380/3/50
Volt/Ph/Hz
Electrical
22
Kw
AHU Power Consumption
400x250x280
Cm
AHU Dimension(LxWxH)
Design criteria: Ambient Temp: 48°F / Entering Air for Dx. coil DB/WB:80/67 °F /Altitude: 0 Ft
General questions
There is no case
Golden Warranty Leaf
10 -year -old after -sales service
Guarantee of the authenticity of the goods
0 Number in Azarbad Warehouse
Optimal energy consumption